Why cannot I find a PowerFlex 753/755 V20 in my Studio/Logix 5000 Software?
This article explains about the New Rev B Control Boards in the PowerFlex 753/755 VFD's and about the AOP for Studio/Logix 5000
Answer:
The PowerFlex 753/755 Control Board has been updated to a Revision B. The firmware for Revision B will start at Version 20.
NOTE: You cannot flash older versions of firmware (below 20) on the new Revision B control boards.
- The Main control board series A will end at Firmware version 16.002
- The Main control board Series B will begin at Firmware version 20.003.
The part number for the Series B main control board:
- PowerFlex 753 = SK-R1-MCB2-PF753
- PowerFlex 755 = SK-R1-MCB2-PF755
No changes to the PowerFlex 755 High HP Frame 8-10
- Series A Main Control Board with Version R16
- Main Control Board Kit = SK-R1-MCB1-F8
NOTE: If you do not see Revision 20+ when configuring the PowerFlex 753/755 AOP in Studio/Logix 5000, verify that you have the latest AOP download in the Rockwell Automation Compatibility & Downloads Center website.