2-Wire Control Non-Reversing (Internal 24VDC Supply)
Parameters:
Port 0: P308 (Direction Mode) to 2 "Rev Disable"
Port 0: P163 (DI Run) to Port 0: P220 (Digital In Sts), bit 1 = Digital In 1
NOTE: Port 0: P150 (Digital In Cfg) will need to be set to 1 "Run Level" if using the same signal for STOP/RUN
View Results:
Port 0: P220 (Digital In Sts) You can verify if input is going ON/OFF
Port 0: P935 (Drive Status 1) You can verify the status of the drive such as STOP ASSERTED, RUN, etc..