How do you wire a PowerFlex 753 for 2-Wire Control?

This article describes how to connect a 2-wire control system to a PowerFlex 753 and the associated parameters

2-Wire Control Non-Reversing  (Internal 24VDC Supply)

How do you wire a PowerFlex 753 for 2-Wire Control?

Parameters:

Port 0: P308 (Direction Mode) to 2 "Rev Disable"

Port 0: P163 (DI Run) to Port 0: P220 (Digital In Sts), bit 1 = Digital In 1

NOTE:  Port 0: P150 (Digital In Cfg) will need to be set to 1 "Run Level" if using the same signal for STOP/RUN

View Results:

Port 0: P220 (Digital In Sts)   You can verify if input is going ON/OFF

Port 0: P935 (Drive Status 1)  You can verify the status of the drive such as STOP ASSERTED, RUN, etc..