- Knowledge Base
- Drives, Motors, & MCC
- Motor Control Centers
What ambient temperature can a Centerline 2100 MCC operate in?
This article details the temperature at which the Centerline 2100 MCC is allowed to operate and be stored at.
Storage and Operation:
CENTERLINE MCCs conform to NEMA standard ICS 1 for service and storage conditions. MCC
ambient operating temperature range is 0…40 °C (32…104 °F) at 95% noncondensing
humidity. Ambient storage temperature range is -30…+65 °C (-22…+149 °F). In addition, MCCs
have an altitude class of 2 km (1 km for MCCs that contain variable-frequency drives).
Reference: Rockwell Automation Publication 2100-IN012L-EN-P